Show simple item record

dc.contributor.advisorCajigas Cerón, Álvaro Andrés
dc.contributor.authorDomínguez Amorocho, María Fernanda
dc.coverage.spatialSeccional Bucaramanga. Universidad Pontificia Bolivariana. Escuela de Ingenierías. Facultad de Ingeniería Ambientalspa
dc.coverage.temporal2010
dc.date.accessioned2013-08-28T16:59:36Z
dc.date.available2013-08-28T16:59:36Z
dc.date.created2010-08-05
dc.date.issued2013-08-28
dc.identifier.urihttp://hdl.handle.net/20.500.11912/848
dc.description68p.: (pdf); il; gráficas; tablas; anexosspa
dc.description.abstractLa optimización de la coagulación floculación de la planta de tratamiento de agua potable de la sede recreacional Campoalegre – Cajasan, tiene como fases de estudio, la determinación del comportamiento de parámetros como la Turbiedad, el color, el pH y la alcalinidad en relación a los eventos de lluvia y a dos fuentes de abastecimiento de la planta, por otra parte, la construcción de diagramas de Coagulación para la remoción de Turbiedad, para la identificación de la zona óptima de remoción del agua predominante en la planta, y finalmente, la determinación de gradientes de velocidad y tiempos de mezcla más favorables para la coagulación-floculación. En el desarrollo del estudio se identificaron las diferencias significativas en la Turbiedad en el periodo lluvioso, así como en la Alcalinidad y el Color en las fuentes. También, la zona óptima de Coagulación se ubicó en un rango pH de 5,5 a 7,5 unidades y a dosis de coagulante de 20 a 40 mg/l, además, el gradiente y tiempo de mezcla rápida fueron de 250RPM (248s-1) y 1 minuto respectivamente, y para mezcla lenta se desarrolló el modelo de la ecuación de Letterman que permitió obtener los gradientes de 2,88s-1 y 3,66s-1 en tiempos de 54 y 35 minutos como óptimos en los periodos de lluvia para la floculación.spa
dc.description.abstractOptimization of coagulation-flocculation processes from the water supply treatment plant of Campoalegre – Cajasan recreational camp, has as study phases, determining the behavior of parameters such as turbidity, color, pH and alkalinity with relation to rainfall events and two sources of plant supply. On the other hand, it has been considerate the design of Coagulation´s Diagrams for turbidity removal, identification of the optimal water removal predominant in the plant and finally, the determination of velocity gradients and mixing times more favorable to coagulation-flocculation processes. As results of the study significant differences in the parameters of turbidity in the rainy season and alkalinity and Color in the sources were identified. Additionally, the optimal coagulation point was set in a pH range from 5.5 to 7.5 units and coagulant dose of 20 to 40 mg / L. The gradient and fast mixing time were 250RPM (248s-1) and 1 minute respectively, while for slow mixing the model from Letterman equation that allowed obtaining the gradients of 2,88s-1 y 3,66s-1 in times of 54 and 35 minutes as optimum in the rainy periods to the flocculation was developed.spa
dc.language.isoes
dc.publisherUniversidad Pontificia Bolivarianaspa
dc.rightsAttribution-NonCommercial-NoDerivatives 4.0 International*
dc.rights.urihttp://creativecommons.org/licenses/by-nc-nd/4.0/*
dc.subjectIngeniería ambientalspa
dc.subjectAgua potablespa
dc.subjectProcesos de potabilizaciónspa
dc.subjectSede recreacional Campoalegre - Cajasan - Tratamiento de aguaspa
dc.titleOptimización de la coagulación - floculación en la planta de tratamiento de agua potable de la sede recreacional Campoalegre - Cajasanspa
dc.typebacherlorThesisspa
dc.rights.accessRightsopenAccessspa
dc.type.hasVersionpublishedVersionspa
dc.identifier.instnameinstname:Universidad Pontificia Bolivarianaspa
dc.identifier.reponamereponame:Repositorio Institucional de la Universidad Pontificia Bolivarianaspa
dc.identifier.repourlrepourl:https://repository.unab.edu.co/