dc.contributor.advisor | Cerón Vivas, Alexandra | |
dc.contributor.author | Forero Torra, Juan Felipe | |
dc.contributor.author | Trigos Duarte, Erwin Fabian | |
dc.coverage.temporal | 2019 | |
dc.date.accessioned | 2021-02-11T17:25:05Z | |
dc.date.available | 2021-02-11T17:25:05Z | |
dc.date.issued | 2019 | |
dc.identifier.uri | http://hdl.handle.net/20.500.11912/8025 | |
dc.description | 75 páginas | spa |
dc.description.abstract | Actualmente en la Planta de Potabilización de Agua Bosconia, del Acueducto Metropolitano de Bucaramanga, se está construyendo un sistema de tratamiento para los lodos generados en los sedimentadores y filtros. Para la puesta en marcha de la planta, es necesario conocer algunos parámetros de operación para el espesamiento y acondicionamiento de lodos, los cuales se
pueden determinar a escala laboratorio. El objetivo de este trabajo fue establecer los parámetros para el acondicionamiento químico y espesamiento de los lodos generados en la planta de agua potable Bosconia. Inicialmente, se estableció la naturaleza del polímero que más se ajustó a los parámetros evaluados para el acondicionamiento químico; además se determinaron parámetros óptimos para el espesamiento del lodo y se determinó la influencia de los polímeros sobre la sedimentabilidad del lodo. El polímero Praestol 2530 de naturaleza aniónica se destacó en las pruebas de acondicionamiento, arrojando dosis óptimas de 7,5 y 9,5 mg/L, tiempo de floculación
óptimo entre 0-3 minutos y finalmente un tiempo de sedimentación óptimo de 4 minutos con bajos valores de turbiedad. Según los resultados obtenidos por las pruebas realizadas durante este estudio se pudo comprobar que el uso de polímeros es eficiente en una muestra de solidos provenientes de una PTAP sin importar la turbidez presente en estas, debido a que los polímeros aniónicos tuvieron un desempeño notable en las pruebas de acondicionamiento y espesamiento del lodo. | spa |
dc.description.abstract | Currently, at the Bosconia Water Potabilization Plant, in the Bucaramanga Metropolitan Aqueduct, a treatment system is being built for the sludge generated in the settlers and filters.
For the plant start-up, it is necessary to know some operating parameters for the thickening and conditioning of sludge, which can be determined on a laboratory scale. The objective of this work was to establish the parameters for the chemical conditioning and thickening of the sludge generated in the Bosconia drinking water plant. Initially, the nature of the polymer that best adjusted to the parameters evaluated for chemical conditioning was established; In addition,
optimal parameters for the thickening of the mud were determined and the influence of the polymers on the sedimentability of the mud was determined. The Praestol 2530 polymer, anionic in nature, performed well in the conditioning tests, yielding optimal doses of 7.5 and 9.5 mg / L per sample, optimal flocculation time between 0-3 minutes for both samples, and finally a time of optimum sedimentation of 4 minutes with low turbidity values. According to the results obtained by the tests carried out during this study, it was possible to verify that the use of polymers is efficient in a sample of solids from a PTAP, regardless of the turbidity present in these, because the anionic polymers had a remarkable performance in the conditioning and thickening tests of
the mud. | eng |
dc.format.mimetype | application/pdf | |
dc.language.iso | spa | |
dc.publisher | Universidad Pontificia Bolivariana | spa |
dc.rights | Attribution-NonCommercial-NoDerivatives 4.0 International | * |
dc.rights.uri | http://creativecommons.org/licenses/by-nc-nd/4.0/ | * |
dc.subject | Lodos | spa |
dc.subject | Potabilización | spa |
dc.subject | Turbiedad | spa |
dc.subject | Acondicionamiento químico | spa |
dc.subject | Plantas para tratamiento de agua | spa |
dc.subject | Empresas - Acueducto Metropolitano de Bucaramanga AMB | spa |
dc.title | Acondicionamiento químico y espesamiento de los lodos producidos en la planta de tratamiento de agua potable bosconia del acueducto metropolitano de Bucaramanga. | spa |
dc.type | Trabajo de grado | spa |
dc.publisher.department | Escuela de Ingenierías | spa |
dc.publisher.program | Ingeniería Ambiental | spa |
dc.type.hasVersion | publishedVersion | spa |
dc.description.sectional | Bucaramanga | spa |
dc.description.degreename | Ingeniero Ambiental | spa |